ABSTRAK
Telah dilakukan penelitian tentang tingkat kebisingan di lingkungan PLTD Lueng Bata Banda
Aceh. Penelitian ini bertujuan untuk mengukur besarnya intensitas bunyi yang bersumber dari
mesin PLTD Lueng Bata pada lokasi dalam lingkungan PLTD yang menjadi tempat konsentrasi
pekerja dan pengguna jasa lainnya seperti kantor administrasi, kantin, rumah karyawan, dan di
luar lingkungan PLTD Lueng Bata. Pengukuran dilakukan dengan waktu sepuluh menit untuk
pengukuran intensitas bunyi dan parameter fisik seperti kecepatan angin dan suhu. Berdasarkan
hasil pengukuran intensitas bunyi yang telah dilakukan di dalam lingkungan PLTD Lueng Bata
didapatkan hasil bahwa nilai pengukuran yang telah melebihi ambang batas baku mutu
Keputusan Menteri Tenaga Kerja No. Kep-51/MEN/1999 di tiga tempat yaitu mesin depan
bangunan mesin utama 98.21 dBA , kantor administrasi 96.89 dBA dan antar mesin 87.46 dBA.
Sedangkan untuk di luar lingkungan PLTD Lueng Bata didapatkan nilai yang melebihi baku
mutu Keputusan Menteri Negara Lingkungan Hidup No.48 Tahun 1996 yaitu 55 decibel dengan
radius 300 sampai dengan 350 meter. Untuk jarak yang melebihi radius tersebut sudah
dipengaruhi oleh kebisingan lingkungan.
Kata kunci : intensitas bunyi, PLTD, fraksi komulatif kebisingan
A study of noise level surounding PLTD Lueng BataBanda Aceh has been done . This study
aims to measure the intensity of the sound that comes from diesel engines at PLTD Lueng Bata
on location in surrounding PLTD, where the diesel is a concentration of workers and users of
other services such as administrative offices, cafeteria, house staff, and outside of Lueng Bata
diesel. Measurements were made in ten minutes to measure sound intensity and physical
parameters such as wind speed and temperature. Based on the results of measurements of the
intensity of the sound done within the diesel Lueng Bata showed that the value has exceeded the
quality standard limits Ministry of Manpower Decree No Kep-51/MEN/1999 in three places,
namely the engine building 98.21 dBA main engine, administration office 98.21 and between
engine 87.46 dBA. As for the outside environment Lueng Bata diesel obtained value exceeds the
quality standards of the Environment Decree 48 of 1996 which is 55 decibels with a radius of
300 to 350 meters. For distances beyond the radius is affected by environmental noise.
Key word : sound intensity, PLTD, faction komulatif noise
Tidak Tersedia Deskripsi
POLA SEBARAN KEBISINGAN DI LINGKUNGAN PLTD (PEMBANGKIT LISTRIK TENAGA DIESEL) LUENG BATA, BANDA ACEH (Arimi, 2013)
SISTEM OPERASI PEMBANGKIT LISTRIK TENAGA DIESEL (ULPTD) LUENG BATA (Junrenal Tamsil, 2023)
OPTIMASI PENJADWALAN OPERASI PLTD PADA PT. PLN (PERSERO) SEKTOR NAGAN RAYA PUSAT LISTRIK LUENG BATA BANDA ACEH DENGAN MENGGUNAKAN METODE ITERASI LAMDA (dani novandi, 2016)
ANALISA TINGKAT KEBISINGAN PERALATAN PRODUKSI TERHADAP KINERJA KARYAWAN (STUDI KASUS: PT PLN KOTA SABANG) (Amirul Mukminin, 2017)
ANALISIS EFISIENSI PEMBANGKIT LISTRIK TENAGA DIESEL DI SEKTOR LUENG BATA (Ruri Nugrahani, 2023)