 <titleInfo>
  <title>PENGARUH PENGGUNAAN KAPASITOR BANK TERHADAP FAKTOR DAYA PADA SISTEM KELISTRIKAN DI RSUD DR. ZAINOEL ABIDIN THE EFFECT OF USE CAPASITOR BANK TO THE POWER FACTOR IN THE ELECTRICAL SYSTEM AT RSUD DR. ZAINOEL ABIDIN</title>
 </titleInfo>
 <name type="Personal Name" authority="">
  <namePart>Surya Rahmad</namePart>
  <role>
   <roleTerm type="text">Primary Author</roleTerm>
  </role>
 </name>
 <typeOfResource manuscript="no" collection="yes">mixed material</typeOfResource>
 <genre authority="marcgt">bibliography</genre>
 <originInfo>
  <place>
   <placeTerm type="text">Banda Aceh</placeTerm>
   <publisher>Universitas Syiah Kuala</publisher>
   <dateIssued>2019</dateIssued>
  </place>
 </originInfo>
 <language>
  <languageTerm type="code">id</languageTerm>
  <languageTerm type="text">Indonesia</languageTerm>
 </language>
 <physicalDescription>
  <form authority="gmd">Null</form>
  <extent></extent>
 </physicalDescription>
 <note>ABSTRACK &#13;
THE EFECT OF USE CAPACITOR BANK TO POWER FACTOR IN THE&#13;
ELECTRICAL SYSTEM AT RSUD dr. ZAINOEL ABIDIN &#13;
&#13;
By &#13;
&#13;
SURYA RAHMAD &#13;
1404005010021&#13;
 &#13;
 The standart power faktor (Cos  ) set  by PLN for customers which uses&#13;
large power faktor is 0,85. If power factor  (Cos  ) is blow 0,85 then the reactive&#13;
power will be measured and taken into account in determining the amount of the&#13;
bill paid. The power factor (Cos  ) which received by RSUD dr. Zainoel Abidin&#13;
is quite low at 0,8, so thet it is not enough the power faktor (Cos  ) requirements&#13;
set by PLN. So RSUD dr. Zainoel Abidin must pay the reactive power. The large&#13;
number of electrical equipment such as electromedics and other electrical devices&#13;
that are inductive causes increated reactive power. There for RSUD dr. Zainoel&#13;
Abidin uses capasitor bank which can correct the power factor (Cos  ). RSUD dr.&#13;
Zainoel Abidin set the standard value of power faktor (Cos  ) 0,95, so there is no&#13;
need to pay for reactive power (kVARh) to the PLN. With capasitor bank at&#13;
RSUD dr. Zainoel Abidin it can suppress reactive power,  so that it can maximize&#13;
avaiblable power usage, reduce overload and reduce losses on the power line.&#13;
Capasitor bank at RSUD dr. Zainoel Abidin has capacity 3x500 kVAR with 12&#13;
steps for each panel. Improving the power faktor, it can maintain the quality of&#13;
health services at RSUD dr. Zainoel Abidin&#13;
&#13;
Keywords: Power Factor,Reactif Power, Capacitor Bank &#13;
</note>
 <classification>0</classification>
 <identifier type="isbn"></identifier>
 <location>
  <physicalLocation>ELECTRONIC THESES AND DISSERTATION Universitas Syiah Kuala</physicalLocation>
  <shelfLocator></shelfLocator>
 </location>
 <slims:digitals/>
</mods>
<recordInfo>
 <recordIdentifier>59946</recordIdentifier>
 <recordCreationDate encoding="w3cdtf">2019-07-11 15:27:40</recordCreationDate>
 <recordChangeDate encoding="w3cdtf">2019-07-11 15:38:49</recordChangeDate>
 <recordOrigin>machine generated</recordOrigin>
</recordInfo>
</modsCollection>