ANALISIS KINERJA SISTEM PEMBANGKIT LISTRIK TENAGA SURYA 50 KWP ON-GRID DI GEDUNG A FAKULTAS TEKNIK UNIVERSITAS SYIAH KUALA
Pengarang
YUSUF DIVA FERNANDO DAMANIK - Personal Name;
Dosen Pembimbing
Ira Devi Sara - 197705252001122001 - Dosen Pembimbing I
Rika Sri Utami - 198803112022032003 - Dosen Pembimbing II
Nomor Pokok Mahasiswa
2104105010057
Fakultas & Prodi
Fakultas Teknik / Teknik Elektro (S1) / PDDIKTI : 20201
Subject
Kata Kunci
Penerbit
Banda Aceh : Fakultas Teknik Elektro., 2025
Bahasa
No Classification
-
Literature Searching Service
Hard copy atau foto copy dari buku ini dapat diberikan dengan syarat ketentuan berlaku, jika berminat, silahkan hubungi via telegram (Chat Services LSS)
Analisis kinerja sistem PLTS 50 kWp on-grid di Gedung A Fakultas Teknik USK dilakukan berdasarkan standar IEC 61724, dengan metode evaluasi pada aspek teknis berdasarkan data operasional history dan real-time yang diperoleh dari iSolarCloud serta validasi menggunakan simulasi software PVsyst. Parameter key performance indicator (KPI) yang dihitung meliputi efisiensi panel surya, efisiensi inverter, final yield, dan performance ratio (PR). Masalah yang diidentifikasi adalah belum pernah dilakukannya evaluasi kinerja teknis sistem PLTS on-grid selama 1 tahun, sehingga penting dilakukan analisis untuk mengetahui sejauh mana sistem telah memenuhi target desain awal dalam menghasilkan energi listrik secara optimal dan melihat kinerja PLTS selama 1 tahun. Tujuan dari penelitian ini adalah
untuk menganalisis kinerja PLTS on-grid selama 1 tahun apakah sudah sesuai dengan yang diharapkan. Metode yang digunakan meliputi pengumpulan data operasional dari iSolarCloud, validasi data menggunakan simulasi PVsyst, serta perhitungan parameter KPI. Hasil evaluasi menunjukkan bahwa efisiensi panel surya untuk keadaan aktual sebesar 21,1% sesuai dengan di datasheet pada kondisi peak sun hour di bulan November 2024, Desember 2024, dan Januari 2025. Efisiensi inverter tercatat sebesar 98,79%, 98,21%, dan 98,35% pada bulan yang sama. Final yield pada Januari 2025 mencapai 3,15 jam. Performance ratio (PR) rata-rata tahunan dari Januari 2024 hingga Januari 2025 adalah sebesar 79,23% dan dapat dikategorikan baik berdasarkan standar ini. Selain itu, orientasi panel juga
berpengaruh terhadap total energi yang dihasilkan. Pada November 2024, modul dengan orientasi utara menghasilkan energi sebesar 767,08 kWh, lebih tinggi dibandingkan dengan modul berorientasi selatan sebesar 510,38 kWh. Kemudian pada Desember 2024, dengan orientasi utara menghasilkan 819,27 kWh dan orientasi selatan 495,17 kWh. Pada Januari 2025, modul dengan orientasi utara menghasilkan energi tertinggi sebesar 851,38 kWh. Dengan demikian, kinerja sistem PLTS 50 kWp dengan sistem on-grid di Gedung A FT USK dapat dinilai baik sesuai dengan standar IEC 61724 yang ditetapkan.
The performance analysis of the 50 kWp solar PV system with an on-grid system in Building A of the USK Faculty of Engineering was carried out based on the IEC 61724 standard, with an evaluation method on technical aspects based on historical and real-time operational data obtained from iSolarCloud and validation using PVsyst software simulation. The key performance indicator (KPI) parameters calculated include solar panel efficiency, inverter efficiency, final yield, and performance ratio (PR). The problem identified is that there has never been an evaluation of the technical performance of the on-grid PLTS system for 1 year, so it is important to analyze to determine the extent to which the system has met the initial design target in producing electrical energy optimally and see the performance of PLTS for 1 year. The purpose of this study is to analyze the performance of on-grid PLTS for 1 year whether it is as expected. The methods used include collecting operational data from iSolarCloud, validating data using PVsyst simulation, and calculating KPI parameters. The evaluation results show that the solar panel efficiency for the actual state of 21.1% is in accordance with the datasheet under peak sun hour conditions in November 2024, December 2024, and January 2025. Inverter efficiency was recorded at 98.79%, 98.21%, and 98.35% in the same month. The final yield in January 2025 reached 3.15 hours. The annual average performance ratio (PR) from January 2024 to January 2025 is 79.23% and can be categorized as good based on this standard. In addition, panel orientation also affects the total energy produced. In November 2024, the north-oriented module produced 767.08 kWh of energy, higher than the south-oriented module of 510.38 kWh. Then in December 2024, the north-oriented module produced 819.27 kWh and the south-oriented module 495.17 kWh. In January 2025, the north-oriented module produced the highest energy of 851.38 kWh. Thus, the performance of the 50 kWp PLTS system with an on-grid system in Building A FT USK can be considered good in accordance with the IEC 61724 standard set.
PERANCANGAN SISTEM PENGENDALIAN ENERGI LISTRIK HYBRID PADA SOLAR HOME (ikram muddin, 2016)
STUDI KELAYAKAN ENERGI MATAHARI SEBAGAI PEMBANGKIT LISTRIK TENAGA SURYA (PLTS) DI PULAU WEH SABANG (Sadam Husin, 2017)
RANCANGAN SISTEM PEMBANGKIT LISTRIK TENAGA SURYA UNTUK POMPA AIR IRIGASI (Mukhtar Riyandri Tarigan, 2019)
MITIGASI HARMONISA PADA PLTS OFF GRID MENGGUNAKAN SHUNT ACTIVE POWER FILTER (SAPF) (Lia Kartika K, 2024)
PERENCANAAN PEMBANGKIT LISTRIK TENAGA SURYA HYBRID GRID-CONNECTED UNTUK GEDUNG B FAKULTAS TEKNIK UNIVERSITAS SYIAH KUALA (SYAUQI MUBARAK, 2025)