ANALISIS RUGI – RUGI DAYA PADA SALURAN TRANSMISI TEGANGAN TINGGI 150 KV DARI GARDU INDUK ULEE KARENG KE GARDU INDUK KRUENG RAYA
Pengarang
QYAN ADAM PRATAMA - Personal Name;
Dosen Pembimbing
Mahdi Syukri - 196812101998021001 - Dosen Pembimbing I
Fathurrahman - 198701052019031009 - Dosen Pembimbing II
Nomor Pokok Mahasiswa
1704105010035
Fakultas & Prodi
Fakultas Teknik / Teknik Elektro (S1) / PDDIKTI : 20201
Subject
Kata Kunci
Penerbit
Banda Aceh : Fakultas Teknik (S1)., 2024
Bahasa
No Classification
-
Literature Searching Service
Hard copy atau foto copy dari buku ini dapat diberikan dengan syarat ketentuan berlaku, jika berminat, silahkan hubungi via telegram (Chat Services LSS)
Listrik merupakan sumber daya yang dibutuhkan dalam kehidupan sehari-hari, baik dalam rumah tangga maupun bisnis, sehingga pendistribusian daya ini harus terjaga kehandalannya agar daya listrik yang sampai ke konsumen dalam kondisi stabil. Namun pada kenyataannya rugi daya sistem transmisi tidak dapat dihilangkan sepenuhnya, dan rugi daya tersebut harus dikendalikan dalam batas normal yang diperbolehkan oleh PLN, yaitu rugi sistem sebesar 5-10%. Penelitian ini menerapkan metode Gauss-Seidel dengan bantuan simulasi pada software ETAP 12.6 untuk menganalisa rugi-rugi daya pada saluran transmisi 150 kV. Hasil penelitian menunjukkan rugi daya sistem masih dalam batas normal, yaitu hanya sebesar 0,54%, namun jatuh tegangan pada bus 4 masih melebihi batas normal, yaitu sebesar 5,4%. Pemasangan kapasitor bank dengan menggunakan metode optimal capacitor placement (ocp) dapat meningkatkan faktor daya serta menurunkan besarnya rugi daya dan jatuh tegangan, pada bus 3 faktor daya sebesar 0,84 menjadi 0,92 setelah pemasangan bank kapasitor, sedangkan rugi daya sebesar 0,53% menjadi 0,46%, serta jatuh tegangan pada bus 4 menjadi 3,5%.
Kata kunci: Rugi Daya, Transmisi, aliran daya, Gauss-Seidel, ETAP, optimal capacitor placement (OCP).
Electricity is a resource needed in everyday life, both in households and businesses, so the distribution of this power must be reliably maintained to ensure that the electricity reaching consumers is stable. However, in reality, transmission system power losses cannot be completely eliminated, and these losses must be controlled within the normal limits allowed by PLN, which is a system loss of 5-10%. This research applies the Gauss-Seidel method with the help of simulation using ETAP 12.6 software to analyze power losses in the 150 kV transmission line. The research results show that the system power loss is still within normal limits, at only 0.54%, but the voltage drop at bus 4 still exceeds the normal limit, at 5.4%. The installation of a capacitor bank using the optimal capacitor placement (OCP) method can improve the power factor and reduce the magnitude of power losses and voltage drops. At bus 3, the power factor increased from 0.84 to 0.92 after the installation of the capacitor bank, while power loss decreased from 0.53% to 0.46%, and the voltage drop at bus 4 became 3.5%. Keywords: Power Losses, Transmission, power flow, Gauss-Seidel, ETAP, optimal capacitor placement (OCP).
ANALISIS SISTEM PROTEKSI DISTANCE RELAY PADA GARDU INDUK 150 KV DI GARDU INDUK ULEE KARENG (AKMARA RAMADHANA BQ, 2024)
PENGARUH PEMASANGAN KAPASITOR BANK TERHADAP TEGANGAN TRANSMISI 150 KV GARDU INDUKRNBANDA ACEH MENGGUNAKAN POWER WORLD SIMULATION (Denny Mairiza, 2024)
STUDI KINERJA STEP VOLTAGE REGULATOR TERHADAP PERBAIKAN TEGANGAN PADA SISTEM DISTRIBUSI 20 KV DI PT.PLN (PERSERO) GARDU INDUK BANDA ACEH (Rahmad, 2014)
STUDI PENGARUH PENAMBAHAN PLTA PEUSANGAN 1 DAN2 4X22MW PADA SUBSISTEM ACEH (Muhammad Arifai, 2016)
STUDI PENGGUNAAN DAN PEMELIHARAAN CURRENT TRANSFORMATOR (CT) 150KV PADA GARDU INDUK (GI) DI BANDA ACEH (Khairul Fuad, 2014)