M. Ikhsan, ANALISIS HASIL PENGUJIAN TAHANAN ISOLASI PADA PMT 150 KV DI GARDU INDUK ULEE KARENG. Banda Aceh Fakultas Teknik Elektro,2024

Abstrak - perangkat dalam sistem proteksi tenaga listrik yang dirancang untuk melindungi peralatan listrik dan orang-orang di sekitar gangguan (korsleting) yaitu pemutus tenaga (pmt). kehandalan pmt khususnya dibagian tahanan isolasi dapat dipengaruhi oleh usia pemakaian sehingga dapat menyebabkan tahanan isolasi pmt beroperasi diluar batas standar. pemeliharaan terhadap pmt perlu dilakukan baik secara elektrik maupun secara manual. pada penelitian ini akan dilakukan analisis hasil pengujian tahanan isolasi pada pmt 150 kv di gardu induk ulee kareng. analisis dilakukan dengan cara mengukur tahanan isolasi kemudian mengukur arus bocor pada pmt dan membandingkannya dengan standar yang digunakan pt. pln yaitu skdir 0520-2.k/dir/2014. nilai resistansi isolasi pada pmt yang terendah tercatat sebesar 44,7 giga ohm pada terminal atas dengan ground (ta-gnd), sementara yang tertinggi juga dalam kondisi off mencapai 489 giga ohm (tb-gnd). resistansi minimum yang diperlukan pada isolator pmt adalah 1,5 giga ohm, dengan nilai tahanan terendah sebesar 44,7 giga ohm. hal ini menunjukkan bahwa seluruh resistansi pmt masih sangat layak digunakan sebagai isolator pada pmt. selain itu, nilai arus bocor yang telah dianalisis tidak melebihi standar yang digunakan oleh pln, yaitu 0,0002 ma. arus bocor terbesar yang tercatat adalah sebesar 0,000114 ma pada fasa ta, sehingga dapat disimpulkan bahwa isolasi tahanan pmt masih layak digunakan berdasarkan besar arus yang bocor melalui isolasi pmt. kata kunci: penguji tahanan isolasi, pemutus tegangan



Abstract

Abstract - The device in an electrical power protection system designed to protect electrical equipment and people from disturbances (short circuits) is known as a circuit breaker (CB). The reliability of a CB, particularly in terms of insulation resistance, can be influenced by its age of use, which may cause the insulation resistance of the CB to operate outside standard limits. Maintenance of the CB needs to be carried out both electrically and manually. This study analyzes the results of insulation resistance tests on a 150 kV CB at the Ulee Kareng substation. The analysis was conducted by measuring the insulation resistance, followed by measuring the leakage current on the CB, and comparing it with the standard used by PT. PLN, which is SKDIR 0520-2.K/DIR/2014. The lowest insulation resistance value recorded on the CB was 44.7 Giga Ohms at the upper terminal to ground (Ta-Gnd), while the highest was 489 Giga Ohms (Tb-Gnd) in the off condition. The minimum resistance required on the CB insulator is 1.5 Giga Ohms, with the lowest measured resistance being 44.7 Giga Ohms. This indicates that all CB resistances are still very suitable for use as insulators in the CB. Additionally, the analyzed leakage current values do not exceed the standard used by PLN, which is 0.0002 mA. The highest recorded leakage current was 0.000114 mA on the Ta phase, leading to the conclusion that the CB insulation resistance is still suitable for use based on the magnitude of the leakage current passing through the CB insulation. Keyword: insulation resistance tester, voltage breaker



    SERVICES DESK