PENGARUH PENGGUNAAN KAPASITOR BANK TERHADAP FAKTOR DAYA PADA SISTEM KELISTRIKAN DI RSUD DR. ZAINOEL ABIDIN THE EFFECT OF USE CAPASITOR BANK TO THE POWER FACTOR IN THE ELECTRICAL SYSTEM AT RSUD DR. ZAINOEL ABIDIN


Pengarang

Surya Rahmad - Personal Name;

Dosen Pembimbing



Nomor Pokok Mahasiswa

1404005010021

Fakultas & Prodi

Fakultas Teknik / Teknik Listrik (D3) / PDDIKTI : 20403

Subject
-
Kata Kunci
-
Penerbit

Banda Aceh : Universitas Syiah Kuala., 2019

Bahasa

Indonesia

No Classification

-

Literature Searching Service

Hard copy atau foto copy dari buku ini dapat diberikan dengan syarat ketentuan berlaku, jika berminat, silahkan hubungi via telegram (Chat Services LSS)

ABSTRACK
THE EFECT OF USE CAPACITOR BANK TO POWER FACTOR IN THE
ELECTRICAL SYSTEM AT RSUD dr. ZAINOEL ABIDIN

By

SURYA RAHMAD
1404005010021

The standart power faktor (Cos ) set by PLN for customers which uses
large power faktor is 0,85. If power factor (Cos ) is blow 0,85 then the reactive
power will be measured and taken into account in determining the amount of the
bill paid. The power factor (Cos ) which received by RSUD dr. Zainoel Abidin
is quite low at 0,8, so thet it is not enough the power faktor (Cos ) requirements
set by PLN. So RSUD dr. Zainoel Abidin must pay the reactive power. The large
number of electrical equipment such as electromedics and other electrical devices
that are inductive causes increated reactive power. There for RSUD dr. Zainoel
Abidin uses capasitor bank which can correct the power factor (Cos ). RSUD dr.
Zainoel Abidin set the standard value of power faktor (Cos ) 0,95, so there is no
need to pay for reactive power (kVARh) to the PLN. With capasitor bank at
RSUD dr. Zainoel Abidin it can suppress reactive power, so that it can maximize
avaiblable power usage, reduce overload and reduce losses on the power line.
Capasitor bank at RSUD dr. Zainoel Abidin has capacity 3x500 kVAR with 12
steps for each panel. Improving the power faktor, it can maintain the quality of
health services at RSUD dr. Zainoel Abidin

Keywords: Power Factor,Reactif Power, Capacitor Bank